1 erstatnings løsning fundet

Eksisterende pumpe - Cirkulation

Fabrikat Perfecta
Produkt navn Delta 125-13/180
Byggelængde 620 mm
Spænding 3x400 V
Pumpehusgange/-flange DN 125 PN16
Nominel effekt 5,5 kW

Udskiftningspumpe - Konventionel Udskiftningblad

Produkt navn Atmos GIGA-I 125/200-7,5/4
Artikelnummer 2220298
MEI ≥ 0,4
IE 3
Byggelængde 620 mm
Spænding 3x400 V
Pumpehusgange/-flange DN 125 PN16
Nominel strøm 14,9 A
Nominel effekt 7,5 kW
Medietemperatur -20 - +140 °C

Bemærkninger

Passer uden krav om ombygning af rørsystemet.
Kontakt Wilo-Teknisk indesalg ved pumpning med glycol eller har speciel materiale krav.

Produktinformation
Atmos GIGA-I 125/200-7,5/4

Atmos GIGA-I 125/200-7,5/4
Artikelnummer : 2220298
VVS-nummer :

Konstruktion
Tørløberpumpe i inline-konstruktion med flangeforbindels.e

Anvendelse
Pumpning af opvarmningsvand (iht. VDI 2035), koldt vand og vand-glykol-blandinger uden slibende substanser i varmtvands-, koldtvands- og kølesystemer.

Tekniske data
  • Tilladt temperaturområde for pumpemediet -20 °C til +140 °C
  • Maks. omgivelsestemperatur 40 °C
  • Nettilslutning 3~400 V, 50 Hz (andre på forespørgsel)
  • Kapslingsklasse IP55
  • Nominel diameter DN 32 til DN 250
  • Standardversion til driftstryk: 13 bar (til +140 °C)/16 bar (til +120 °C)
Materialer
  • Pumpehus og lanterne: Standard: EN-GJL-250;
  • Pumpehjul: Standard: EN-GJL-200; specialudførelse: Bronze CuSn 10 rustfrit stål 1.4408
  • Aksel: 1.4122
  • Akseltætning: AQEGG, andre glideringstætninger på forespørgsel
Konstruktion
Et-trins lavtrykscentrifugalpumpe i inline-konstruktion med:
  • Akseltætning
  • Flangetilslutning med trykmålingstilslutning R 1/8
  • Lanterne
  • Kobling
  • IEC-standardmotor
Leveringsomfang
  • Pumpe
  • Monterings- og driftsvejledning
Flange gasket DN 125 PN6/10
Artikelnummer: 2529886
VVS-nummer:
Flange gasket DN 125 PN6 / 10, Klingersil:
  • Thickness: 2 mm.
  • Inner diameter: 142 mm.
  • Outer diameter: 195 mm.
Difference pressure sensor 10 m
Artikelnummer: 2136454
VVS-nummer:

The differential pressure sensor kit enables dp-c and dp-v control of the frequency-controlled high-pressure centrifugal pumps.
The sensor measures the differential pressure between the suction ports and discharge ports to the pipes, and converts this into an electrical signal 4-20 mA, which is used by the frequency converter to regulate the pressure of the pump. The value of the output current is proportional to the differential pressure.
Difference pressure sensor 20 m
Artikelnummer: 2136456
VVS-nummer:

The differential pressure sensor kit enables dp-c and dp-v control of the frequency-controlled high-pressure centrifugal pumps.
The sensor measures the differential pressure between the suction ports and discharge ports to the pipes, and converts this into an electrical signal 4-20 mA, which is used by the frequency converter to regulate the pressure of the pump. The value of the output current is proportional to the differential pressure.
Difference pressure sensor 40 m
Artikelnummer: 2136458
VVS-nummer:

The differential pressure sensor kit enables dp-c and dp-v control of the frequency-controlled high-pressure centrifugal pumps.
The sensor measures the differential pressure between the suction ports and discharge ports to the pipes, and converts this into an electrical signal 4-20 mA, which is used by the frequency converter to regulate the pressure of the pump. The value of the output current is proportional to the differential pressure.
Difference pressure sensor 60 m
Artikelnummer: 503184696
VVS-nummer:

The differential pressure sensor kit enables dp-c and dp-v control of the frequency-controlled high-pressure centrifugal pumps.
The sensor measures the differential pressure between the suction ports and discharge ports to the pipes, and converts this into an electrical signal 4-20 mA, which is used by the frequency converter to regulate the pressure of the pump. The value of the output current is proportional to the differential pressure.
Difference pressure sensor 100 m
Artikelnummer: 503184799
VVS-nummer:

The differential pressure sensor kit enables dp-c and dp-v control of the frequency-controlled high-pressure centrifugal pumps.
The sensor measures the differential pressure between the suction ports and discharge ports to the pipes, and converts this into an electrical signal 4-20 mA, which is used by the frequency converter to regulate the pressure of the pump. The value of the output current is proportional to the differential pressure.
Frekvensomformer EFC-7,5 kW 3~
Artikelnummer: 2550228
VVS-nummer: